Experience In MotionUSER INSTRUCTIONSInstallationOperationMaintenanceMX/DDC-100 Field Unit FCD LMENIM2329-01 – 03/11
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11102.2.3 Host ControllerIn the DDC-100 system, the network can be connect
11MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-00 – 2/08flowserve.com2.2.4 Master Station IIA Master Station II may be used in t
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11122.2.5 Network CableThe network consists of a shielded, twisted-pair ca
13MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comBelden 3105A SpecificationsTotal cable length between repeat
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11142.3.2 Modbus Function CodesThe controlling device (master) must confor
15MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comMessage BreakdownQuery Response03 Slave (Field Unit) Addres
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1116Table 2.3 – Status Bit Definitions (continued)Bit NumberModbus Bit Addre
17MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comTable 2.3 – Status Bit Definitions (continued)Bit NumberModb
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1118Table 2.4 – Register definitionsRegister # Description Meaning1 Comma
19MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comTable 2.4 – Register definitions (continued)Register # Desc
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/112MX/DDC-100 Field Unit Installation and Operation Manual©2011 Copyright L
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1120Table 2.4 – Register definitions (continued)Register # Description Mea
21MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comMessage BreakdownQuery Response7D Slave (Field Unit) Addres
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1122Message BreakdownQuery Response46 Slave (Field Unit) Address 46 Slave (
23MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comExample of force coil commandForce coil 1 of field unit 49 O
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1124Table 2.6 – Modbus 06 command and field unit holding register 40001Host
25MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comExample of “Move-To” CommandMove an actuator at address 179
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1126To move the actuator to a position of 50%, place the value 0x4B in the
27MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comMessage BreakdownQuery Response03 Slave (Field Unit) Addres
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1128Message BreakdownQuery Response01 Slave Address 01 Slave Address0F Func
29MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comExample of “Move-To” CommandMove an actuator at address 1 t
3MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comContents1 Introduction 51.1 Purpose 51.2 How to Use thi
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1130Installation and Configuration3.1 Site and Network Cable Preparation 3.
31MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.com3. Clean earth-ground connection (less than 5 ohms) enhan
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11322. Separate the cable parts. Unbraid the shield and peel back the foil
33MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.com4. Apply heat shrink tubing to insulate the drain wire and
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11346. Connect the network cables to the MX terminal block as shown in Fig
35MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.com3.1.2.2 Network Cable Connection to Host Controller or Mast
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1136Figure 3.8 – Redundant bi-directional loop topology Daisy Chain The da
37MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comFigure 3.9 – Daisy chain topologyLegendMOVN/CData terminal
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11383.2 Installation Verification3.2.1 Network Cabling Installation Verific
39MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.com3.3 Field Unit ConfigurationThe actuator has been configured
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/114FiguresFigure 1.1 – Typical DDC-100 system with or without a Master Stat
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11403.3.1.2 Changing DDC Parameters Enter the “CHANGE SETTINGS” mode and “C
41MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comDDC AddressThe network address must be entered in accordanc
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11421. “CHANGE MODUTRONIC?”2. Select “YES.”3. “STATUS (ON) – OK?”4. Select
43MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comTable 3.6 – Digital input voltagesTerminal # Minimum “ON”
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11443.4 Configuration ConfirmationField unit operation cannot be verified unt
45MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comThis page is intentionally blank.
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1146Associated DocumentsMX Actuator Quick Start-Up Instructions (MX Actuat
47MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comThis page is intentionally blank.
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1148Troubleshooting1. Refer to Appendix A, Wiring Diagram.2. With power off
49MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comCAUTION: a There is potential to cause electrostatic damag
5MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comIntroduction1.1 PurposeThis manual explains how to install
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1150How to Order PartsTo order parts or obtain further information about yo
51MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comThis page is intentionally blank.
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1152Appendix – Wiring DiagramFigure A.1 (1 of 2) – Typical MX/DDC-100 wirin
53MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comFigure A.1 (2 of 2) – Typical MX/DDC-100 wiring diagramREMO
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1154 Figure A.2 - MX Terminal blockGROUNDINGLUGNETWORK GROUNDINGLUGS
55MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comThis page is intentionally blank.
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1156Appendix – MX/DDC Register DefinitionsRegister 1 Command register. Write
57MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comScaling chosen through LCS “CHANGE DDC?” subroutine “ANALOG
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1158Bit 13 Close Torque Switch Fault – Indicates an overtorque condition wh
59MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comBit 15 Closing in Local Mode – Monitors the actuator LCS Cl
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1161.4 User KnowledgeIt is recommended that the user read this manual in i
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1160Register 12Digital Inputs 1 register. Read-only. 16-bit unsigned value.
61MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comBit 03 Analog Input 2 Lost - Indicates analog Input 2 is no
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1162Appendix – Typical DDC-100 Network Installation AssignmentsVarious pro
63MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comSystem Integrator TasksDeliverable From To CommentsSpecifica
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/1164Contractor TasksDeliverable From To CommentsSpecifications Engineer Cont
65MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.comLimitorque TasksDeliverable From To CommentsSpecifications E
flowserve.comFlowserve CorporationFlow ControlUnited StatesFlowserve Limitorque5114 Woodall Road, P.O. Box 11318Lynchburg, VA 24506-1318Phone: 434-528-
7MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.com1.6 General SpecificationsDirect-to-Host Specifications:Direc
MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/118System Components2.1 IntroductionThis section gives an overview of the
9MX/DDC-100 Field Unit Installation and Maintenance FCD LMENIM2329-01 – 03/11flowserve.com2.2.1 MX ActuatorThe MX is a multi-turn valve actuator desi
Komentarze do niniejszej Instrukcji