MX/QX FOUNDATION Fieldbus Field Unit FCD LMENIM2330-01 – 08/11
6
1.5 MX/QX FF System Capabilities and Features
Limitorque’s FOUNDATION fieldbus field unit conforms to the open fieldbus standard IEC 61158.
It is suitable for use on the Fieldbus H1 highway and uses a twisted-pair cable for connection to
the highway. The communication system theoretically supports up to 240 actuators with the use of
repeaters.
The MX/QX FF field unit fits in the actuator in the sealed electrical housing. Adjustments to the
MX/QX FF settings may be made over the FOUNDATION fieldbus data highway using a network
configuration tool.
The MX/QX FF unit may command its actuator and others to:
Open
Stop
Close
Move to a set position
Perform an emergency shutdown operation
Read and control relays
Perform partial stroke test
Monitor analog inputs and position
Monitor modes and alarms
Commands to the unit come over the network from the host system, which may be:
Personal Computer (PC)
Distributed Control System (DCS)
Programmable Logic Controller (PLC)
Field Device Tool (FDT) w/ Device Type Manager (DTM)
Some other microprocessor-based device
Commands may also be generated in another network actuator or device and transmitted over
fieldbus using peer-to-peer, consumer/producer communication.
The MX/QX FF also has the capacity of being a Link Active Scheduler (LAS) on a FOUNDATION
Fieldbus network. It can be configured either for Basic or LAS mode. In BASIC mode, the MX/QX will
display COMM LOSS if power is removed from the FF field unit. In LAS mode, the MX/QX will display
HARDWARE FAILURE if power is removed from the FF field unit.
A fieldbus device is an intelligent device within the actuator that can send multiple variables to
the control system over a high-resolution and distortion-free digital communication network. The
device provides control and self-test capabilties, which allows abnormal conditions to be easily and
immediately identified before an unplanned shutdown.
Additional features and capabilities are:
The system reduces the cost of wiring and installation – existing wiring and multi-drop connections
can be used
The devices are interoperabledevices from different suppliers can communicate with one another
on the same network.
A typical MX/QX FF system is shown in Figure 1.1.