Flowserve PMV Valve Control System Instrukcja Użytkownika Strona 8

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 20
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 7
Manual F5
– 8 –
Installing F5-EX on P5/EP5
Installing on an actuator
Remove front cover, indicator and Allen head screw from the positioner.
Install drive coupling 4 and secure it with the Allen head screw.
Remove front covers and indicator from the F5-EX unit.
Remove screws 3.
Install F5-EX on P5/EP5, , make sure drive coupling is properly engaged
before tightening screws 5.
Reinstall and tight screws 3. Connect and calibrate.
Reinstall front covers and indicator.
Front cover screws 2 shall be tightened to 7 Nm (5,2 lbf x ft)
Remove front covers and indicator from the F5-EX unit.
Remove screws 3 and (5). Reinstall and tight screws 3.
Install drive shaft into F5-EX, a solid click should be heard when spindle
adapter is properly installed.
Mount F5-EX on the actuator using the F05 holes and a mounting kit.
Connect and calibrate, reinstall front covers and indicator.
Front cover screws 2 shall be tightened to 7 Nm (5,2 lbf x ft).
4
5
3
2
3
2
Przeglądanie stron 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 19 20

Komentarze do niniejszej Instrukcji

Brak uwag