n Combination spanner 7 mm A. F., DIN 3113, form B
n Combination spanner 10 mm A. F., DIN 3113, form B
n Combination spanner 13 mm A. F., DIN 3113, form B
n Combination spanner 16 mm A. F., DIN 3113, form B
n Combination spanner 17 mm A. F., DIN 3113, form B
n Torque spanner 1 – 12 Nm, ISO 6789
n Torque spanner 8 – 40 Nm, ISO 6789
n Torque spanner 80 – 400 Nm, ISO 6789
n Punch 14.8 x 220 CuZn (brass)
n Hammer 300 g, Din 1041
n Self-centering pulling device, size 0
Maintenance – continued –
Tools
Torques
Item
Continuous blowdown valve
Torque required
for tightening [Nm]
DN 15-32 DN 40,50
A
BA 46, BA 47, BAE 46, BAE 47 7 11
O
BA 46, BA 47, BAE 46, BAE 47 130
P
BA 46, BA 47, BAE 46, BAE 47 5 11
R
BA 46, BA 47, BAE 46, BAE 47 7
T
BA 46, BA 47, BAE 46, BAE 47 20
7
BAE 46, BAE 47 7
Changing packing and internals of BAE 46, BAE 47 – continued –
22. Screw hexagon nut T onto the threaded part of the nozzle stem R and tighten with a torque
of 20 Nm while holding the control lever.
23.
Screw sealing plug O together with gasket N into the valve body and tighten with a torque of
130 Nm or screw in the sample valve with the gasket according to the instructions given by the
manufacturer.
24.
Put coupling 8 onto control lever U and fix the mounting bracket 5 and actuator 1 to the valve
body using the hexagon screws 7. Adjust control lever until the coupling makes contact.
25.
Align the actuator, making sure that the coupling 8 is level on the control lever. Fasten hexagon
screws 7 with a torque of 7 Nm.
26.
Adjust the switching cams for OPEN, CLOSED and OPERATING POSITION or, if fitted, the feedback
potentiometer according to the attached installation manual “Actuators EF...”.
27.
Set the switching cam for CLOSED in the actuator such that the torque checking pin 6 is to the
right but does not touch the checking hole.The closing torque in this position is 10 Nm. Fig. 13
All torques indicated in the table are based on a room temperature of 20 °C.