Establishing Functions
Select function
Before installing and commissioning the NRGS 15-1 ascertain the settings for the
required functions.
Five functions are available:
Function 1
Electrode rod 1 Low level 1 / burner off
Electrode rod 2 Low level 2
Electrode rod 3 Timed pump control (fill control) tv=0 30 sec.
Electrode rod 4 High level
Function 2
Electrode rod 1 Low level 1 / burner off with test and reset button
Electrode rod 2 Low level 2
Electrode rod 3 Timed pump control (fill control) tv=0 30 sec.
Electrode rod 4 High level
Function 3
Electrode rod 1 Low level alarm 1 / burner off
Electrode rod 2 Feed pump on (fill control)
Electrode rod 3 Feed pump off (tv=0 sec.)
Electrode rod 4 High level
Function 4
Electrode rod 1 Low level alarm 1 / burner off with test and reset button
Electrode rod 2 Feed pump on (fill control)
Electrode rod 3 Feed pump off (tv=0 sec.)
Electrode rod 4 High level
ON
1
23
5
4 678910
ON
1
23 54 678910
ON
123 54 678910
ON
123 54 678910