Valve block
Turn off the air and electric power
supply before starting any work.
Release the connector F from the proces-
sor pcb.
¥ R emove the four screws I.
¥ L ift out the valve block
N.B. Do not disassemble the valve block
¥ When installing the valve block Ñ torque
the four screws to 1,4 Nm and sealwith
L ocktite 222.
Silencer
A silencer, L (option) can be mounted under
the plate M on the D3. Contact PMV .
Spindle adapter
The spindle adapter can be changed to suit
the actuator in question, see page 9.