Limit 2 See Limit 1.
temp Alarm based on temperature.
On/Off Temperature alarm on/off.
Low temp Temperature low limit setting
High temp Temperature high limit setting
Hysteresis Allowed hysteresis.
Alarm on Select ON/OFF offers output on terminals.
Valve act Behaviour of valve when alarm is generated
Valve act
No action Alarm generated only. Operations no affected.
Goto open C+ gives full pressure and valve moves to fully open position. Positioner
changes to position Manual.
Goto close C- gives full pressure and valve moves to fully closed position. Positioner changes to
position Manual.
Manual Valve stays in unchanged position. Positioner moves to position Manual.
Alarm limit 1 on
Alarm limit 2 on
Alarm limit 1 off
Alarm limit 2 off
Alarm limit 2 on
Alarm limit 2 off
Alarm limit 1 off
100%
0%
Limit 1 max
Hysteresis
Limit 2 max
Hysteresis
Hysteresis
Limit 2 min
Hysteresis
Limit 1 min
Alarm limit 1 on