AXENIM0048-01 (Firmware Rev. Nov. 12 99) (AUTO-48) 11/01 Page 12 of 16
©2001, Flowserve Corpor
ation, Springville, UT
Flowserve Corporation 1350 South Mountain Springs Parkway Phone: 801 489 2233
Flow Control Division Springville, Utah 84663 Facsimile: 801 489 2228
Automation Business Unit www.flowserve.com Email: [email protected]
Automax Valve Automation Systems
Product S
pecification
Rel.
Index
Parameter Factory
Default
Description
25 OPERATION Note 1 Configures the piezo/coil elements for single or dual coil operation.
Single Readback (single coil devices only) permits digital feedback
of switch status to DO-1 Function Block.
26 OUTPUT_CONFIGUR
ATION
Note 1 Configures the piezo/coil signals to shut-off or remain energized
after TIME_OUT period. Applies to Dual Coil mode only.
27 ODOMETER This variable counts the transitions from open to closed and
closed to open states. It is reset-able to 0, after maintenance.
28 RESET_ODOMETER Resets the ODOMETER counter.
29 FAILURE_RECOVERY Enable/Disable FAILURE_RECOVERY action.1: Act with or
without change in the input, 2: Do not act until a new change in the
input.
30 RESET_TIMEOUT Resets a TIME_OUT occurrence.
31 TRANSITION_TIME How much time for the last transition.
32 TIME_OUT 10 The time allowed for a transition before the DI associated with the
TIME-OUT Alarm is Activated. Also, the length of the One-Shot
pulse voltage output to the coils in the Dual Coil Operation Mode.
33 CLOSED_SWITCH SW1 state
34 OPEN_SWITCH SW2 state
35 TRANSITION_ALARM DI-1 state = transition TIME-OUT state;
36 EXTERNAL_ALARM DI-2 state = It read the status of the external input. Data is passed
on to DI-2.
37 ACTION_TIME Time since last command for transition.
Notes:
1. Selected by Factory in accordance with customer PO specifications.
Transducer Block Parameter Specifications
Rel.
Index
Parameter Mnemonic Data
Type
Size Valid
Range
Units Class
1 ST_REV Unsigned 16 2 Positive N/A Read
2 TAG_DESC Visible String 32 String Data N/A R/W
3 STRATEGY Unsigned 16 2 N/A R/W
4 ALERT_KEY Unsigned 8 1 1-255 N/A R/W
5 MODE_BLK DS-69 4 N/A R/W
6 BLOCK_ERR Bit String 2 N/A Read
7 UPDATE_EVT DS-73 5 N/A Read
8 BLOCK_ALARM DS-72 13 N/A Read
9 TRANSDUCER_DIRECTORY Unsigned 16
Array
Variable N/A Read
10 TRANSDUCER_TYPE Unsigned 16 2 E Read
11 XD_ERROR Unsigned 8 1 N/A Read
12 COLLECTION_DIRECTORY Unsigned 32
Array
Variable N/A Read
13 FINAL_VALUE_D DS-66 2 N/A R/W
14 ACT_FAIL_ACTION Unsigned 8 1 0=Undefined
1=Close
2=Open
3=Last
E R/W
15 ACT_MAN_ID Unsigned 32 4 E Read
16 ACT_MODEL_NUM Visible String 32 String Data N/A Read