Automax Logix 3200IQ Digital Positioner
Installation, Operation and Maintenance Instructions
Mounting the Positioner
CAUTION: Positioner shaft is spring-loaded and
features mechanical stops at each end of stroke.
Failure to follow these procedures carefully may
result in severe damage to positioner. Read through
entire procedure before starting.
1. Attach positioner mounting bracket to actuator using
fasteners supplied with bracket (Figure 4). Tighten
bolts finger-tight only at this time.
2. Install coupler (if required – coupler is not required
for NAMUR mounting) on actuator shaft, making sure
it is centered.
Figure 4: Linear Mark One Control Valve Mounting
3. Stroke the actuator to determine direction of rotation
as shown in Figure 5. Pay specific attention to the slot
that will engage positioner shaft.
Figure 5: Actuator Shaft
4. Carefully grasp positioner shaft with pliers as shown in
Figure 6. Turn shaft to determine direction of rotation.
Figure 6: Turn Positioner Shaft